SANWA · Clamp Meters
DLC470
Leakage clamp with 0.01 mA resolution and band-pass filter.
- 0.01 mA leakage
- 400 A AC
- CAT III 600 V
The SANWA DLC470 is a multifunction leakage clamp meter for users measuring small AC leakage currents in milliamps. A band-pass filter extracts mainly the 50/60 Hz component, and MAX/MIN hold records the extremes. It also measures AC current to 400 A, voltage and resistance. Bhumika quotes this model for Canada.

Features
- Leakage current (ACmA) with 0.01 mA resolution
- Band-pass filter (BPF) extracts mainly the 50/60 Hz component
- MAX/MIN value hold
- Auto power off (30 min., cancelable)
- AC current to 400 A, plus voltage, resistance and continuity
Specifications
| AC leakage current | 60.00 mA / 600.0 mA; ±(1.2%+5); resolution 0.01 mA |
|---|---|
| AC current | 60.00 A / 400.0 A; ±(1.2%+5); resolution 0.01 A |
| AC voltage | 600.0 V; ±(1.2%+5); resolution 0.1 V |
| DC voltage | 600.0 V; ±(1.0%+2); resolution 0.1 V |
| Resistance | 999.9 Ω; ±(1.0%+8); resolution 0.1 Ω |
| Continuity | Buzzer sounds at 30 Ω or below; open voltage approx. 0.9 V |
|---|---|
| Display | 6000 (A/V); 9999 (Ω) |
| Sampling rate | 2 times/sec. |
| Bandwidth | 40–400 Hz |
| Rating | IEC61010 CAT. III 600 V |
|---|
| Clamp diameter / conductor size | Φ35 mm / 10 × 40 mm |
|---|---|
| Battery | LR03 × 2 |
| Battery life | Approx. 42 hrs. (alkaline battery, backlight off) |
| Dimensions | H206 × W83 × D38 mm |
| Mass | Approx. 320 g |
Standard accessories
- TL-21a test lead
- C-DCM660 carrying case
Optional accessories
- CL-14 adapter
- CL-15a adapter
- TL-9IC adapter
- CL-DG3a adapter
- TL-A7M2 adapter
- TL-A4 adapter